plc automation

Hotline

Yokogawa YTA610 Temperature Transmitter Field Mount

description:The YTA610 is the highly accurate temperature transmitter that accepts Thermocouple, RTD, ohms or DC millivolts inputs and converts it to a 4 to 20 mA DC or Fieldbus signal for transmission....
BASIC INFO

Yokogawa YTA610 Temperature Transmitter Field Mount  

The YTA610 is the highly accurate temperature transmitter that accepts Thermocouple, RTD, ohms or DC millivolts inputs and converts it to a 4 to 20 mA DC or Fieldbus signal for transmission.
The YTA610 supports HART® and FOUNDATION fieldbusTM communication protocols.HART types are certified as complying with SIL 2 for safety requirement.

 

The YTA610 provides high accuracy, stability, and reliability. The housing structure adopts reliable dual-compartment structure. The sensor input can be choice of single or dual inputs. This input can accept the RTD, thermocouple, ohm, or DC millivolt. It converts the sensor input to a 4 to 20 mA DC analog signal or Fieldbus digital signal. HART® 7 Protocol or FOUNDATION™ Fieldbus ITK 6 version are available. The dual input can accept two sensors calculation of the differential or average value and the sensor backup function. Sensor backup functions for automatically switches-over from the primary to the backup upon sensor failure.
By adoption of local parameter switch on the Indicator, it becomes easy to do the on-site setting work.
 

YTA610 features include:

  • Dual-compartment field-mount housing
  • Choice of HART® 7, or FOUNDATION™ Fieldbus ITK 6 Protocol
  • Local Parameter Setting function (Indicator model)
  • Basic diagnosis


STANDARD SPECIFICATIONS
PERFORMANCE SPECIFICATIONS
Accuracy
HART communication type:
A/D accuracy/span + D/A accuracy
(See Table 1 on page 4.)
Fieldbus communication type:
A/D accuracy (See Table 1 on page 4.)
Cold Junction Compensation Accuracy
± 0.5°C (± 0.9 °F) for T/C only
Ambient Temperature Effect (per 10°C change)
±0.1% or ±(Temperature coefficient/span), whichever
is greater. (See Table 2 on page 5.)
Stability
RTD: ±0.1% of reading or ±0.1°C per 2 years,
whichever is greater at 23±2°C.
T/C: ±0.1% of reading or ±0.1°C per year, whichever
is greater at 23±2°C.
5 Year Stability
RTD: ±0.25% of reading or ±0.25°C,
whichever is greater at 23±2°C.
T/C: ±0.5% of reading or ±0.5°C,
whichever is greater at 23±2°C.
Vibration Effect
The YTA610 is tested to the following specifications
with no effect on performance per IEC 60770-1
10 to 60 Hz 0.21 mm peak displacement
60 to 2000 Hz 3g
Power Supply Effect
±0.005% of calibrated span per volt

 


 

-----------------------------------